Madagas Gas Solenoid Valve
MVD/5
Technical Description
The MVD/5 series safety solenoid valves are single-stage automatic shut-off valves that meet the requirements of EN 161 for gas burners and gas equipment.
- Max. operating pressure up to 200, 360 or 500 mbar (20, 36 or 50 kPa)
- MVD: fast opening
- Main volume adjustable(MVD/MVDLE)
Gas solenoid valves at home and abroad are divided into three categories in principle
One, direct acting gas solenoid valve: electromagnetic coil electromagnetic force to close the piece from the seat, gas solenoid valve working principle: when energized.Valve open;Power, electromagnetic force dissipation, the spring to close the pressure on the seat, the valve closed.But the diameter is generally not more than 25mm solenoid valve features: vacuum, negative pressure, zero pressure can work normally.
Two, spread the direct acting gas solenoid valve: when there is no pressure difference between the inlet and the inlet, the working principle of the gas solenoid valve: a direct acting and pilot type combined principle.After the power, the electromagnetic force directly to the pilot valve and the main valve closed parts in turn up, the valve opened.When the inlet and outlet to start the differential pressure, after the power, the electromagnetic force pilot valve, the main valve chamber pressure rise, the pressure falls on the chamber, so as to use the differential pressure to push the main valve upward;Power, the pilot valve using spring force or medium pressure to push the sealing parts, moving down, so that the valve closed.But the power is larger, solenoid valve features: zero pressure difference or vacuum, high pressure can also be * action.Request required horizontal device.
Three, pilot gas solenoid valve: gas solenoid valve to open the pilot hole, gas solenoid valve working principle: when energized.The pressure of the upper chamber drops rapidly, and the pressure difference of the upper, lower and higher is formed around the sealing part. The fluid pressure pushes the sealing part upward, and the valve opens;Power, the spring force to the pilot hole closed, the inlet pressure through the bypass hole agile chamber in the close valve around the formation of low and high pressure difference, fluid pressure to push the closed parts move down, close the valve. Can be installed at will (to be customized) but must meet fluid differential pressure conditions.
MVD/5
Madagas Gas Solenoid Valve, normally when closed, fast opening, fast closing, manual limitation of flowing gas volume by adjusting main volume.
Specifications | |
Nominal diameters |
DN15 |
Max. operating pressure |
360 mbar (36 kPa) or up to 500 mbar (50 kPa) - refer to type overview |
Solenoid valve |
Valve as per EN 161, Class A, Group 2, single-stage mode |
Closing time |
< 1 s |
Opening time |
< 1 s |
Fast stroke |
Adjustable |
Main volume adjustment |
Manually adjustable on MVD |
Materials of gas-conveying parts |
Housing: aluminium, steel, brass |
Voltage/frequency |
230 V AC (+10 % -15 %); 50-60 Hz - other voltages on request |
Rating / power consumption |
Refer to type overview |
Switch-on duration |
100 % |
Degree of protection |
IP 54, IP 65 on request |
Switching rate |
MVD…/5: max. 1000/h |
Measuring/ignition gas connection |
G 1/4 ISO 118, on both sides in inlet section, additionally G 3/4 on input side, form size DN 40 (flange) upwards |
Dirt trap |
Sieve installed, mesh width 1 mm |
Ambient temperature |
-15 ° C to +60 °C |
Installation position |
Solenoid from vertically upright to horizontally lying |
Closed position signal contact |
MVD/5 Type K01/1, DIN-tested, mountable on DN 10 - DN 150 |
Valve proving system |
Type VDK 200 A S02, mountable via G 1/4 test connection, Type VPS 504, mountable with adapter up to DN 80 |
Type |
pmax. |
DN / Rp |
Solenoid-No. |
Pmax. |
I max. |
Opening time |
Dimensions |
Weight |
|||||
øa |
b |
c |
d |
e |
f |
||||||||
MVD 205/5 |
360 |
Rp 1/2 |
100 |
17 |
0,08 |
< 1 s |
50 |
80 |
90 |
75 |
113 |
150 |
1,00 |
Operation and assembly instructions
Solenoid valve
One stage operation
Type MVD …/5
Type MVDLE …/5
Nominal diameters
Rp 3/8 – Rp 2 1/2
DN 20 – DN 100
MVD 205/5
Setting the main flow
Changing solenoid MV 205/5
1. Remove dust cap A.
2. Replace solenoid Note solenoid no. and volt age!
3. Screw on dust cap A.
We reserve the right to make any changes in the interest of technical progress.