TitleProduct

PVC Insulated Cable

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Shandong

  • Validity to:

    Long-term effective

  • Last update:

    2020-01-14 14:31

  • Browse the number:

    136

Send an inquiries
+
Baoshida International Holding Group Co., Ltd.
Contactaixin:

baoshida(Mr.)  

Email:

telephone:

phone:

Arrea:

Shandong

Address:

8 Kaiyuan Road, Licheng District, Jinan, Shandong, China.

Website:

http://www.baoshida-group.com/ http://baoshida.gdbaizhong.com/

+

PVC Insulated Cable

XLPE Insulated Power Cable with Rated Voltage up to 35kV


I. Application

This product is fit for power transmission with rated voltage up to 35kV.


II. Type and Designation

Type

Designation

Standard

Copper core

Aluminum core

YJ(S)V

YJL(S)V

XLPE insulated PVC sheathed power cable

IEC60502-2

GB/ T12706.2〜.3

YJ(S)Y

YJL(S)Y

XLPE insulated PE sheathed power cable

YJV22

YJLV22

XLPE insulated steel tape armoured PVC sheathed power cable

YJV32

YJLV22

XLPE insulated fin steel wire armoured PVC sheathed power cable

YJV42

YJLV42

XLPE insulated fine steel wire armoured PVC sheathed power cable

YJ(S)V62

YJL(S)V62

XLPE insulated dual non-magnetic metal tape armoured PVC sheathed power cable

YJ(S)V72

YJL(S)V72

XLPE insulated non-magnetic metal tape armoured PVC sheathed power cable


III. Specification

Type

Number of core

Rated voltage kV

3.6/ 6、6/ 6

6/10、8.7/10、

8.7/15

12/20

18/30、21/35、26/35

Nominal cross-section mm2

YJ(S)V

YJ(S)Y

YJ(S)V62

YJ(S)V72

YJL(S)V

YJL(S)Y

YJL(S)V62

YJL(S)V72

1

25〜1600

25-1600

35-1600

50〜1600

YJV

YJY

YJV22

YJV32

YJV42

YJLV

YJLY

YJLV22

YJLV32

YJLV42

3

25 〜500

25〜500

35〜500

50〜500


IV. Structural Figure


V. Insulation Thickness

Nominal cross­section mm2

U。/U(Um) Nominal insulation thickness at rated voltage

3.6/ 6 (7.2) kV

6/ 6 (72) kV
6/ 10 (12) kV

8.7/ 10 (12) kV 8.7/ 15 (17.5) kV

12/ 20 (24) kV

18/ 30 (36) kV

21/ 35 (40.5) kV

26/ 35 (40.5) kV

25

2.5

3.4

4.5

35

2.5

3.4

4.5

5.5

50〜185

2.5

3.4

4.5

5.5

8.0

9.3

10.5

240

2.6

3.4

4.5

5.5

8.0

9.3

10.5

300

2.8

3.4

4.5

5.5

8.0

9.3

10.5

400

3.0

3.4

4.5

5.5

8.0

9.3

10.5

500〜1600

3.2

3.4

4.5

5.5

8.0

9.3

10.5


Ⅵ. Technical Parameter

DC resistance of the conductor can comply with regulation in IEC60228、GB/T3956.

Inductance and earthing capacitance

Inductance and capacitance of single cable


Nominal cross- section

mm2

voltage rating kV

3.6/6

6/6、6/10

8.7/ 10、 8.5/ 15

12/20

18/30

21/35

26/35

Inductance

Capacitance

Inductance

Capacitance

Inductance

Capacitance

Inductance

Capacitance

Inductance

Capacitance

Inductance

Capacitance

Inductance

Capacitance

25

0.240

0.24

0.433

0.19

0.449

0.15









35

0.408

0.26

0.411

0.21

0.427

0.18

0.459

0.16







50

0.385

0.30

0.398

0.24

0.414

0.19

0.436

0.17

0.448

0.13

0.467

0.12

0.513

0.11

70

0.366

0.34

0.379

0.27

0.392

0.22

0.414

0.19

0.432

0.15

0.455

0.14

0.487

0.12

95

0.344

0.38

0.354

0.30

0.369

0.24

0.392

0.21

0.413

0.16

0.436

0.15

0.465

0.13

120

0.331

0.42

0.344

0.32

0.360

0.26

0.379

0.23

0.394

0.17

0.417

0.16

0.446

0.14

150

0.315

0.46

0.334

0.35

0.350

0.28

0.366

0.25

0.398

0.19

0.404

0.17

0.430

0.15

185

0.308

0.50

0.322

0.38

0.341

0.30

0.350

0.27

0.375

0.20

0.392

0.18

0.417

0.16

240

0.301

0.54

0.313

0.42

0.325

0.34

0.341

0.29

0.361

0.22

0.376

0.20

0.394

0.18

300

0.296

0.56

0.302

0.47

0.314

0.37

0.328

0.32

0.341

0.24

0.360

0.22

0.373

0.19

400

0.295

0.61

0.299

0.55

0.309

0.41

0.318

0.36

0.332

0.26

0.347

0.23

0.361

0.21

500

0.288

0.68

0.291

0.63

0.298

0.45

0.307

0.41

0.328

0.32

0.355

0.25

0.354

0.23

630

0.281

0.76

0.283

0.71

0.289

0.51

0.298

0.45

0.312

0.34

0.339

0.30

0.342

0.26


Other Electrical Performance

Rated voltage
U./U

kV

3.6/6

6/ 6 6/ 10

8.7/ 10
8.7/ 15

12/ 20

18/ 30

21/ 35

26/ 35

Route test









Partial discharge
Voltage discharged

kV
pc

6.3
10

10.5
10

15.2
10

20.9
10

31.2
10

36.4
10

45.0
10


A.C voltage test

time

kV
min

12.5
5

21
5

30.5
5

42
5

63
5

73.5
5

91
5

Type test









Partial discharge
Voltage discharged

kV
PC

6.3
5

10.5
5

15.2
5

20.9
5

31.2
5

36.4
5

45.0
5

Impact voltage test

kV

60

75

95

125

170

250

250

4hours A.C voltage test

kV

14.4

24

34.8

48

72

84

104


Ⅶ. Feature

1. XLPE insulated cable has good electrical and heat resistant performance.

2. Compared with oil filled cable, it has no risk of oil leakage, and cable laying will not effected by the fall.

3. It can bear long-term operating network voltage, and various over voltage encountered in the normal operating, such as over voltage by operation, by the atmosphere, by the fault.

4. It can transmit the power reliable.

5. It has good mechanical strength, bending, and corrosion, destroy flame-retardant performance.

6. It has no pollution, and has a long usage life.


Ⅷ. Working Condition

1. Max .operating temperature of the conductor: 90°C.

2. In short circuit condition (Max .continual period shall not exceed 5s), Max. temperature of the conductor shall not exceed 250°C.

3. Laying surrounding temperature 0°C.

4. Permitted bend radius of the cable: shall not less than 15 times of outer diameter of the cable for the single cable, and shall not less than 20 times of outer diameter of the cable for three core cable.